NIEU is defined as the key national university, co-built by Jiangsu Provincial Government and China Meteorological Administration(CMA). This university is located in capital Nanjing with beautiful scenery and ancient culture.
Now, this university plans to utilize high efficient and energy-saving air source heat pump water heater for five building hot water supply. See Details below:
Heat pump unit configuration
1. Reference Standard
Design Standard:
GB/T18713—2002 Technical Code for The Design, Installation & Acceptance of Heat Pump System
GB/T6424—1997 Technical Specifications of Air-source Heat Pump
GB/T4271—2000 Methods of Measuring the Performance of Air-source Heat Pump
GB/T15513—1995 Air Source Heat Pump Evaluating Method
Design and Installation of Air Source Heat Pump & Water Heating System
QB/T15816—2004 "Installation Standards for Heat Pump System"
Construction and Installation Standards for Heat Pump System
GB50015-2003 "Design Code for Water & Drainage Engineering of Buildings"
GBJ 9-87 Loading Code for Design of Building Structures
2. Design Project
▲Design Parameter:
Climate condition: Considering cold wether in winter but meeting hot water supply in winter, lowest ambient temp. is set as 5℃.
Make-up water temp. Lowest:5℃; heating extent:50℃
Watered temp.: rated hot water temp.:55℃
Design mode: cycling constant hot water and make-up water heated
Unit normally average working hours: on base of 10-18 hours
▲ Water Consumption:
"Design Code for Water & Drainage Engineering of Buildings" GB50015-2003 as a rule, water consumption below:
| Series | Building title | person or bed / day | Top daily water consumption (L) | Operating timing(H) |
| 1 | Domitory Self-prepared hot water supply and shower installation; Central hot water supply and shower installation; |
per person per day per person per day | 40~80 L 60~100 L |
24hrs |
| 2 | Villa | per person per day | 70~110 L |
24hrs |
| 3 |
Single person and students dormitory; Reception hotel, Training center, General hotel; |
per person per day; |
25~40L 40~60L 50~80L 60~100L |
24hrs |
| 4 |
Hotel and Guest room |
Per bed per day; |
120~60L 40~50L |
24hrs |
| 5 |
In-patient Department |
Per bed per day Per bed per day Per bed per day |
60~100L 70~130L 110~120L |
24hrs |
According to basic information above, 125 T water consumption per day, in total, equipping five heat preservation water tank, stainless steel, each volume 25T.
Heat pump unit:
10 units- RS-200-12G recirculating high efficient heat pump water heater unit
System equipment and Water tank Choice
Unit: Compressor-American top brand Copeland, function stable, noise low, technique reference advantageous over other same type, 15 years guarantee.
Electronic valve: American top brand Alco, all units tested,no leaking before deliver; automatic defrosting function.
Heat preservation water tank: Stainless steel material, PU foam technique inside, hardness and good effect for warmth. This technique is nowadays the state of the art in the world. More or less 5 ℃ temp. tolerance in 24 hrs
Piping and accessory: PPR piping,joint,valve,etc. All accessory from domestic top products, owning quality testing report.
Heating preservation material: piping heat preservation uses rubber and plastic,one of most excellent material.
Automatic controlling system: Unit control is automatic system, applied in water level of tank, temperature, heating cycling and automatic on and off, reaching the purpose of energy conservation and emission reduction and reliable operation.
Heat pump performance reference
Unit title: Dibetter air source heat pump water heater
| Techical parameter | |
| Standard working condition:20℃ | |
| Model | RS-200-12G |
| Rate Input | 9765W |
| Heating Capacity | 38280W |
| Power | 380VAC/50HZ |
| Rate Current | 18.5A |
| Hot water offer | 55℃ |
| working ambient temp | -5℃~40℃ |
| make-up hot water frequency | 823L/h |
| coolant | R22 |
| (COP)COP% | 400% |
| Duct Diameter | DN40 |
| Size | 1450×705×1315 |
| Net weight | 325 kg |
| Hot water Equipment | Dibetter heat pump unit | Electrical water heater | Gas water heater | Diesel oil boiler |
| Energy consumption | Electricity | Electricity | gas | Diesel oil |
| Environment Pollution | No | No | Gas Exhaust | Diesel Exhaust |
| Safety | Safe | electrothermal tube aging; short circuit hidden trouble | Gas leaking,fire,exploding,etc |
Oil leaking,fire,exploding,etc |
| Unit Life | 14~16 years | 6~8 years | 6~8years | 6~8years |
| Energy Equipment Type | Total Thermal required | Unit(kcal/kg) | Energy Consumption | Energy unit price | Energy expenses per day |
||||
| Gas water heater Thermal efficiency 75% |
5000,000kcal | ÷ | 7,072kcal/kg | = | 70kg | × | 6.2yuan/kg | = | RMB 4383 yuan |
| Diesel boiler Thermal efficiency 75% |
5000,000kcal | ÷ | 6,612kcal/㎏ | = | 756㎏ | × | 6.5yuan/㎏ | = | RMB 4914 yuan |
| Electricwaterheater thermal efficiency 90% |
5000,000kcal | ÷ | 774kcal/degree | = | 6460degree | × | 0.9yuan/degree | = | RMB 5814 yuan |
| Dibetter air source HPWH thermal efficiency 400% |
5000,000kcal | ÷ | 3,440kcal/D G | = | 1453degree | × | 0.9yuan/degree | = | RMB 1308 yuan |